Accredited by EHVRC
Tests done as per IEC61439-6
1. Temperature Rise. Subclause 10.10
Pass, Achieving 37 degrees above ambient.
2. Power-Frequancy Withstand Voltage. Subclause 10.9.2
Pass
3. Impulse Withstand Voltage. Subclause 10.9.3
Pass @ 9.8KV
4. Resistance to Abnormal Heat and Fire Due To Internal Electric Effects. Subclause 10.2.3.2, AKA Glow Wire Test ( IEC 60695-2-10)
Pass @ 950 degree without flaming.